Technical Parameter Requirements For Surge Protectors Installed On 35kv Lines
The technical parameters of metal oxide surge protective device insulators installed on 35kV lines generally must meet the following requirements:
① Continuous operating voltage (RMS) not less than 40.8kV;
② Rated voltage (RMS) of surge protector insulators not less than 51kV;
③ DC 1mA reference voltage not less than 73kV (range: 73-74kV);
④ Residual voltage (peak value) at a standard discharge current of 5kA not greater than: 134kV for lightning impulse, 114kV for switching impulse, and 154kV for steep wave impulse.