Understanding SPD Ratings: In, Imax, Iimp, Uc and Up
When comparing surge protection devices, the electrical ratings printed on the product or listed in its datasheet provide essential information about performance and application.
However, a 40 kA SPD is not necessarily more suitable than a 20 kA SPD. The meaning of each rating, the associated test waveform and the system conditions must all be understood.
This guide explains the key electrical parameters used in IEC-based surge protection specifications.
Overview of Important SPD Ratings
| Symbol | Symbol | What It Describes |
| In | Nominal discharge current | Surge current capability under defined 8/20 μs test conditions |
| Imax | Maximum discharge current | Maximum declared 8/20 μs discharge current for applicable test requirements |
| Iimp | Impulse discharge current | Lightning impulse current capability with defined charge and specific energy |
| Uc | Maximum continuous operating voltage | Maximum continuous voltage applicable to the SPD protection mode |
| Up | Voltage protection level | Declared voltage-limiting performance |
| Itotal | Total discharge current | Current through the common protective earth or PEN path during the applicable total current test |
What Is In in a Surge Protection Device?
In is the nominal discharge current of an SPD, expressed in kiloamperes.
It is associated with an 8/20 μs current waveform and is an important parameter for evaluating surge discharge performance under specified testing conditions.
For example, a Type 2 surge protection device may be declared with In = 20 kA.
This value does not mean that the SPD can carry a continuous current of 20 kA. It relates to a short-duration surge current under defined test conditions.
What Is Imax?
Imax is the maximum discharge current associated with the applicable 8/20 μs test requirements.
A Type 2 SPD may have In = 20 kA and Imax = 40 kA. These values describe different aspects of its discharge performance and must not be treated as interchangeable.
When selecting an SPD, Imax should be considered together with In, Up, operating voltage and the required protection type.
A higher Imax alone does not establish better equipment protection or a longer service life.
What Is Iimp?
Iimp is the impulse discharge current used to characterize Type 1 lightning-current capability.
In addition to the current peak, the lightning impulse test involves defined charge and specific energy characteristics. The 10/350 μs waveform is commonly used to represent these conditions.
An SPD with Iimp = 12.5 kA cannot be directly compared with an SPD having Imax = 40 kA by comparing only the numerical current values.
The different waveforms produce different electrical and thermal stresses.
What Is Uc?
Uc is the maximum continuous operating voltage that can be applied to the relevant SPD protection mode under its specified conditions.
The selected Uc must be compatible with the actual operating voltage of the electrical system and the voltage appearing across the protective path.
For AC applications, Uc is generally expressed as an RMS voltage. For photovoltaic SPDs, the corresponding PV operating voltage parameter is commonly identified as Ucpv.
Selecting an SPD with an unsuitable operating voltage can expose the protective components to excessive continuous electrical stress.
What Is Up?
Up is the voltage protection level declared for the surge protection device. It characterizes the SPD's ability to limit voltage under the relevant test conditions.
A suitable Up must be selected in relation to the impulse withstand capability of the equipment requiring protection.
The actual voltage appearing at the protected equipment may be higher than the declared Up because of voltage drops and induced voltages associated with the connection conductors.
For this reason, installation layout and conductor length are important parts of effective surge protection.
It is also important to distinguish the declared Up of a finished SPD from a residual voltage measurement obtained during an individual laboratory test.
Understanding Itotal in Multi-Pole SPDs
Multi-pole surge protection devices may have a declared total discharge current, Itotal.
This parameter addresses the current flowing through the common PE or PEN connection during the applicable total current test.
Itotal should not be automatically calculated by multiplying a single-pole current rating by the number of protective modules. Internal circuit topology, current distribution and the capability of common protection paths must be considered.
The declared total current rating should be supported by the applicable product documentation and test results.
Surge Current Rating vs Short-Circuit Current Rating
Another important distinction is the difference between surge discharge current and short-circuit current capability.
In, Imax and Iimp describe transient surge performance. The short-circuit current rating, ISCCR, addresses the prospective fault current for which the SPD and its specified disconnecting arrangement are rated.
Both may be expressed in kiloamperes, but they relate to different electrical conditions and test requirements.
How to Compare Two SPDs Correctly
Consider two illustrative Type 2 devices:
| Parameter | Device A | Device B |
| In | 20 kA | 20 kA |
| Imax | 40 kA | 40 kA |
| Uc | 275 V AC | 275 V AC |
| Up | 1.5 kV | 1.8 kV |
Although the devices have identical declared discharge current ratings and operating voltages, their voltage protection levels are different.
Before selecting either device, the purchaser must also consider protection modes, short-circuit rating, backup protection, applicable certificates and installation requirements.
These values are illustrative and do not represent the certified ratings of a specific MDAY product.
Conclusion
SPD ratings describe different aspects of surge protection performance. A reliable selection requires understanding how the parameters work together rather than focusing on one current or voltage value.
MDAY provides detailed electrical specifications for its surge protection devices to help customers compare products according to their actual application requirements.
Explore our AC and DC SPD ranges to review the ratings and technical documentation of specific product models.