SPD Wiring Configurations and Earthing Systems Explained
The number of poles on a surge protection device is only one part of its electrical configuration. To select the correct SPD, it is necessary to understand the protective paths inside the device and the earthing arrangement of the electrical installation.
This guide explains common AC SPD configurations, including 1+0, 2+0, 3+0, 4+0, 1+1 and 3+1, and how they relate to different power distribution systems.
Understanding Protection Modes
An SPD protection mode describes the electrical connection between the conductors across which surge protection is provided.
Common protection modes include:
-
L-N: line to neutral.
-
L-PE: line to protective earth.
-
N-PE: neutral to protective earth.
-
L-L: line to line.
Different SPD configurations provide different combinations of these protection paths.
The external terminal count does not necessarily describe every internal protective component or the complete protection capability.
Understanding Earthing Systems
TN-S System
In a TN-S system, the neutral conductor N and protective earth conductor PE are separate throughout the relevant installation.
SPD protection may involve connections between live conductors and PE, or between phase conductors and neutral with an additional N-PE protection path.
TN-C System
A TN-C system combines neutral and protective functions in a PEN conductor.
SPD configurations must be appropriate for this combined conductor arrangement. In a three-phase TN-C section, a three-path connection between the phase conductors and PEN is commonly used.
TN-C-S System
A TN-C-S system combines neutral and protective functions in part of the supply network and separates them in another part.
The appropriate SPD depends on whether it is installed before or after the separation of the PEN conductor.
TT System
In a TT system, the installation's protective earthing arrangement is separate from the supply neutral earthing arrangement.
The selection of protection modes, SPD position relative to residual current devices and disconnection behavior must comply with the applicable installation requirements.
A 1+1 or 3+1 configuration is commonly considered for suitable TT installations.
IT System
In an IT system, the source is isolated from earth or connected to earth through an impedance.
SPD selection requires particular consideration of voltage-to-earth conditions, including those that can arise during an earth fault.
A standard TN-system SPD should not automatically be assumed to be suitable for an IT system.
Common AC SPD Wiring Configurations
The following table describes typical configurations. Actual product connection diagrams and manufacturer instructions take priority.
| Configuration | Typical protection arrangement | Common application examples |
| 1+0 | One protective path between a conductor and its reference conductor | Individual protection mode |
| 2+0 | Two direct protective paths | Suitable single-phase systems |
| 3+0 | Three phase conductors connected through individual protection paths to PE or PEN | Three-phase systems without a separate neutral protection path |
| 4+0 | L1, L2, L3 and N connected through individual paths to PE | L1, L2, L3 and N connected through individual paths to PE |
| 1+1 | L-N protective path plus N-PE protective path | Suitable single-phase TN-S or TT arrangements |
| 3+1 | Three L-N protective paths plus a common N-PE protective path | Suitable three-phase TN-S or TT arrangements |
These naming conventions are widely used in the SPD industry. They should always be interpreted together with the manufacturer's circuit diagram.
What Is the Difference Between 3+1 and 4+0 SPDs?
In a typical 4+0 configuration, each phase conductor and the neutral conductor has its own protective path to PE.
In a typical 3+1 configuration, the three phase conductors are protected through L-N paths, with an additional common N-PE path.
The N-PE component in many 3+1 devices uses voltage-switching technology, such as a spark gap or gas discharge tube.
The two configurations can have different characteristics in relation to leakage current, temporary overvoltage behavior, combined protection modes and installation suitability.
Neither configuration is universally better. The selection depends on the system conditions and verified product characteristics.
What Are CT1 and CT2?
IEC-based installation practice also uses connection arrangements commonly identified as CT1 and CT2.
CT1 generally involves protection paths between live conductors and the protective conductor. CT2 generally combines protection paths between phase conductors and neutral with an additional neutral-to-protective-conductor path.
A typical 4+0 arrangement illustrates the CT1 principle, while a typical 3+1 arrangement illustrates the CT2 principle.
The appropriate arrangement depends on the earthing system and the specific installation requirements.
Installation Considerations
Correct SPD wiring involves more than selecting the right pole configuration.
Connecting conductors should be arranged to minimize additional voltage during a surge. Protective bonding must be effective, and the installation must include the required overcurrent and fault protection.
The location of the SPD, conductor cross-section, connection length and coordination with residual current devices must follow the applicable installation standards and manufacturer instructions.
Remote signalling and status indication may also be considered where continuous monitoring is important.
Do AC SPD Configuration Names Apply to DC SPDs?
Not necessarily.
AC configuration names generally describe arrangements involving phases, neutral and protective earth.
DC surge protection devices use different circuit structures based on the positive and negative conductors, earthing conditions and the internal protective topology.
A two-pole or three-pole DC SPD should therefore be selected using its actual circuit diagram rather than assuming it is equivalent to an AC configuration with the same number of modules.
Conclusion
Selecting the correct SPD wiring configuration requires understanding the protection modes, earthing system and installation conditions.
MDAY offers AC surge protective devices in multiple connection configurations to support different electrical distribution systems.
Always review the specific product wiring diagram and technical documentation before selecting or installing an SPD.