How To Choose A Dc Surge Protection Device For Solar PV Systems

Publish Time: Author: Site Editor Visit: 1

Photovoltaic installations are exposed to transient overvoltages caused by lightning activity and electrical switching events. Outdoor PV arrays, long DC cables and sensitive inverter electronics make surge protection an important consideration in solar power system design.

Choosing the correct DC surge protection device requires an understanding of the PV system voltage, lightning exposure, protection modes and fault conditions.

This guide explains the key factors to consider when selecting an SPD for the DC side of a photovoltaic installation.

1. Select an SPD Designed for Photovoltaic Applications

A solar PV array is not electrically equivalent to a conventional AC supply or a battery-fed DC system.

Its current-voltage characteristics and fault behavior require appropriate protective components and disconnection arrangements.

IEC 61643-31 establishes product requirements and test methods for SPDs intended for the DC side of photovoltaic installations rated up to 1,500 V DC.

IEC 61643-32 provides selection, installation and coordination principles for SPDs in photovoltaic systems.

When comparing DC surge protectors, verify that the selected device is intended for the PV application and that its technical documentation covers the required electrical conditions.

2. Determine the Maximum PV System Voltage

The operating voltage rating of a PV SPD must be compatible with the maximum voltage that can appear across its protective paths.

The maximum continuous operating voltage of a PV SPD is identified as Ucpv.

PV string voltage depends on the number of connected modules, the electrical characteristics of each module and the environmental conditions.

In particular, PV module open-circuit voltage generally increases as module temperature decreases.

A string described as a 1,000 V system may therefore require additional evaluation of its actual maximum open-circuit voltage.

Example: Evaluating a PV String

Consider an illustrative PV string consisting of 20 modules, each with an open-circuit voltage of 49.5 V under standard test conditions.

The combined open-circuit voltage under these conditions is: 20 × 49.5 V = 990 V

If the calculated cold-weather increase in string voltage is 10%, the maximum string voltage would be: 990 V × 1.10 = 1,089 V

An SPD with Ucpv = 1,000 V would not be suitable for this assumed maximum voltage.

This example demonstrates why selecting an SPD solely from the nominal system voltage is insufficient.

The actual calculation must use the module manufacturer's temperature coefficient, the minimum design temperature, applicable tolerances and the relevant installation requirements.

The inverter's maximum DC input voltage and other equipment ratings must also be checked.

3. Choose Between Type 1 and Type 2 PV SPDs

A Type 2 PV SPD is commonly used where protection against induced lightning surges and other transient disturbances is required.

Its discharge performance is characterized by ratings such as In and Imax using the 8/20 μs current waveform.

A Type 1 or combined Type 1+2 PV SPD may be necessary where partial lightning currents can enter the DC installation.

The presence of an external lightning protection system, separation distance, bonding arrangement and potential lightning current paths must be evaluated.

The decision should be based on the installation's lightning protection concept rather than the size of the PV installation alone.

4. Check the Voltage Protection Level

The declared voltage protection level Up should be appropriate for the impulse withstand capability of the equipment being protected.

This is particularly important for solar inverters, which contain sensitive power electronic components.

Connecting conductor length and installation geometry can increase the voltage stress at the equipment beyond the value measured at the SPD terminals.

A correctly selected DC SPD must therefore be combined with a suitable connection and bonding arrangement.

5. Evaluate Protection Modes and PV Circuit Configuration

PV systems use positive and negative DC conductors, together with an earthing arrangement appropriate to the system design.

Depending on the SPD topology, protection may be provided between positive and negative conductors and between these conductors and protective earth.

Y-type and other circuit arrangements may be used to achieve the intended protection modes and operating voltage characteristics.

The number of SPD modules does not by itself determine its suitability for a specific PV system.

Always review the manufacturer's connection diagram, Ucpv rating and protection mode specifications.

6. Check PV Fault Current and Disconnection Requirements

A PV SPD must operate safely under the relevant fault conditions.

Important considerations include the PV short-circuit current rating, the internal disconnection arrangement and any required external protective device.

The selected SPD must be compatible with the prospective PV short-circuit current at the point of installation.

A discharge current rating such as Imax = 40 kA does not describe the device's continuous PV fault-current capability.

These are separate performance requirements.

7. Determine the Correct Installation Location

PV surge protection may be required at several points within a solar power system.

Typical locations include:

  • PV array or string connection points.

  • DC combiner boxes.

  • Inverter DC input terminals.

  • AC distribution boards connected to the inverter output.

The need for multiple SPDs depends on cable length, lightning exposure, equipment withstand voltage and coordination requirements.

The AC side and DC side of the inverter should be evaluated separately because they have different electrical characteristics.

8. Practical PV SPD Selection Checklist

Before selecting a photovoltaic surge protection device, confirm:

Selection item Information required
Maximum PV voltage Calculated maximum open-circuit voltage
SPD operating voltage Suitable Ucpv rating
Protection type Type 1, Type 2 or combined classification as required
Discharge capability In, Imax and Iimp where applicable
Voltage limitation Suitable Up rating
Protection modes Positive, negative and earth connections
Fault conditions Compatible PV short-circuit and disconnection ratings
Installation Location, conductor arrangement and coordination
Product documentation Applicable standard, certificate and installation instructions

Conclusion

Choosing a DC SPD for solar PV systems involves much more than selecting a 600 V, 1,000 V or 1,500 V product.

The correct device must be suitable for the actual maximum PV voltage, lightning exposure, protection modes and fault conditions of the installation.