News

How to Select a Backup Fuse or Circuit Breaker for a Surge Protection Device

Publish Time: Author: Site Editor Visit: 1

A surge protection device is designed to limit transient overvoltages, but it may also be exposed to sustained electrical faults within the power system.

Appropriate backup protection helps ensure that a failed SPD or its associated circuit can be disconnected safely.

Selecting a backup fuse or circuit breaker requires more than matching the surge current rating printed on the SPD.

Why Does an SPD Need Backup Protection?

Most power-system SPDs are connected in parallel with the electrical circuit.

Under normal operating conditions, the protective path remains in a high-impedance state. During a transient overvoltage, it becomes conductive and diverts surge current.

If a protective component deteriorates or fails, an abnormal current may flow through the SPD branch.

Backup protection is used to address relevant overcurrent and short-circuit conditions and to support safe disconnection according to the SPD's verified design.

Many MOV-based SPDs incorporate internal thermal disconnectors. These disconnectors respond to particular thermal overload conditions but should not automatically be considered a replacement for external short-circuit protection.

Some SPD designs include integrated backup protection. Whether additional external protection is required depends on the product documentation and installation conditions.

Understanding F1 and F2

A typical parallel-connected SPD installation may involve two overcurrent protective devices.

  • F1: The existing upstream protective device of the electrical installation.

  • F2: An additional protective device installed in the SPD branch when required.

Whether a separate F2 device is necessary depends on the characteristics of F1, the SPD manufacturer's specified backup protection and the requirements of the connecting conductors.

An existing upstream protective device may be sufficient in certain installations if it meets the manufacturer's specified conditions.

What Is the Maximum Backup Fuse Rating?

An SPD manufacturer may specify a maximum permissible backup fuse rating, together with the fuse type or other required characteristics.

For example, a hypothetical SPD may be documented for a maximum upstream backup fuse of 125 A gG.

If the existing upstream protective device exceeds this permitted rating, an appropriately coordinated branch protective device may be required.

However, the actual selection must also consider the prospective short-circuit current, conductor protection and the manufacturer's installation instructions.

The maximum backup fuse rating should not be interpreted as a universal recommended fuse size for every installation.

Why Imax Cannot Determine the Backup Fuse Size

The maximum discharge current Imax describes the SPD's ability to withstand an applicable short-duration surge current waveform.

A fuse rating, such as 63 A or 125 A, relates to its current-carrying and interruption characteristics under specified conditions.

These ratings describe different electrical phenomena.

A 40 kA SPD does not automatically require a particular fuse size. Two SPDs with the same Imax may have different approved backup protection arrangements because their internal construction and verified fault behavior differ.

The surge withstand capability of the backup fuse must also be considered. An excessively small fuse may operate during a surge and disconnect the protective path.

Can a Circuit Breaker Replace a Backup Fuse?

A circuit breaker may be used for SPD backup protection where the combination is suitable and supported by the relevant manufacturer documentation.

However, a circuit breaker and a fuse with the same nominal current rating do not necessarily have equivalent operating characteristics.

Relevant factors include:

  • Breaking capacity.

  • Time-current characteristic.

  • Surge impulse withstand.

  • Energy let-through.

  • Coordination with the SPD and upstream protection.

A fuse specified by an SPD manufacturer should not be replaced with an arbitrary circuit breaker of the same current rating without verifying suitability.

Check the Short-Circuit Current Rating

The SPD's short-circuit current rating, ISCCR, is an important safety parameter.

It describes the prospective fault-current conditions for which the SPD and its specified disconnecting arrangement are rated.

The prospective short-circuit current at the SPD installation point must be compatible with the verified arrangement.

For example, an SPD may have a surge discharge rating of 40 kA but a different short-circuit current rating.

The two values must not be confused simply because both are expressed in kiloamperes.

A Practical Backup Protection Selection Procedure

When selecting SPD backup protection, follow these steps:

  1. Identify the exact SPD model and its installation instructions.

  2. Check the maximum permitted upstream protective device.

  3. Determine the prospective short-circuit current at the installation point.

  4. Confirm the permitted fuse or circuit breaker characteristics.

  5. Check the protection requirements of the SPD connection conductors.

  6. Verify coordination with upstream protective devices.

  7. Confirm whether an additional SPD branch protective device is required.

This approach helps ensure that the protection arrangement can withstand the intended surge conditions while providing appropriate fault protection.

Backup Protection for DC and PV SPDs

DC and photovoltaic applications require additional attention to source characteristics and fault interruption.

The absence of periodic natural current zero crossings can affect how electrical arcs are extinguished.

For PV SPDs, the short-circuit characteristics of the PV array and the manufacturer's specified disconnection arrangement must be considered.

An AC backup fuse or circuit breaker recommendation should not be transferred directly to a DC SPD unless the protective device and combination are verified for the actual DC application.

Conclusion

Correct SPD backup protection depends on the complete protective arrangement, not just the SPD's Imax rating.

The manufacturer's specified backup device, prospective short-circuit current, connecting conductors and surge withstand requirements must all be considered.

MDAY provides technical specifications for its surge protection devices and offers supporting electrical protection products, including circuit breakers and fuses.

Consult the documentation of the selected SPD model to identify a compatible backup protection arrangement for your electrical system.

Recent News
Recommended products
WhatsApp us

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.