News

Surge Protective Device Parameter Introduce

Publish Time: Author: Site Editor Visit: 228

Basic Parameters

Parameter name Parameter symbol Noun interpretation
Maximum continuous operating voltage UC The maximum AC voltage RMS or DC voltage that can be safely and continuously applied to the SPD.
Voltage protection level UP A performance parameter that characterizes the voltage between SPD limit terminals, whose value can be selected from a list of priority values.  This value should be greater than the maximum limit voltage.
Transient overvoltage UT Test voltage applied to SPD for a specified time [ 5s and 120min ] without failure or abnormality, UT > UC.  The TT distribution system requires an additional test to simulate a transient " high" over voltage between the neutral and PE ( TOV)(, 1200 Vac applied at 300 A for 200 ms ): compliance with this test requires the use of a CT2 mounting system ( special high energy withstand gas discharge tubes between N and PE ).
Maximum discharge current In In is the peak 8 / 20 μ s pulse current that the T1 or T2 SPD can withstand repeatedly ( 15 shocks ) without damaging it.
Nominal discharge current Imax Imax applies to the T2 test SPD and is the peak of 8 / 20 μ s pulse current flowing through the SPD without damaging it.
Impulse current Iimp Iimp is suitable for T1 SPD test and is the maximum impulse current ( 10 / 350 μ s ) that surge protection device can withstand without damaging it.  This test simulates the impact on an AC power surge protector after a facility is directly struck by lightning.

Figure 1 SPD Parameter Explanation

Selection of UC and UT

The maximum continuous working voltage UC of SPD depends on the nominal voltage ( UO ) of AC network and distribution system ( TN, TT, IT );  The level of transient overvoltage UT is related to UC.  Also, resistance to " high pressure" TOV ( 1200 Vac, 300 A, 200 ms ) is required between the neutral point of TT system and PE.

AC system 230/400Vac
Power distribution system TT TN IT
UC Required Minimum 255 255 440
Transient overvoltage UT 335/440 335/440 -
Transient overvoltage N / PE 1200 - -

Figure 2

Selection of Iimp 

The impulse current Iimp is defined for Class T1 SPD. According to IEC 60364 - 5 - 534, the minimum value of single stage Iimp is required to be 12.5 kA, which is defined according to actual application conditions.  For T1 SPD, our company can provide 3 impulse current values Iimp: 12.5 kA, 25 Ka and 50 Ka.

Condition Iimp Model
Very high risk areas 50kA MYCH50-AC T1
Severe thunderstorm area 25kA MYCH25-AC T1
High and low thunderstorm areas 12.5kA MYCH12.5-AC T1+T2

Figure 3

Selection of In 

According to the standard requirements, the minimum In value of SPD at the facility inlet ( LPZ interface or equipment front end ) is 5kA ( 8 / 20 μ s waveform ), but higher nominal discharge current is recommended in high thunderstorm area, which can prolong the service life of SPD.  Imax ( maximum discharge current ) is related to the In value.

 

Condition In Model
 Very high risk areas >20kA MYN60-AC T2
 Severe thunderstorm area 10-20kA MYN40-AC T2 MYN20-AC T2T3
 High and low thunderstorm areas <5kA -

Figure 4

Selection of UP 

The user must select the UP of the SPD that matches the rated impulse voltage withstand value (UW ) of the equipment.  In general, the lower the UP, the better the protection.

 According to IEC 60364, the voltage protection level of SPD at 230 / 400 Vac grid incoming line shall not be greater than 2.5 kV: this value also meets the requirements of rated impulse voltage tolerance ( UW ) of electromechanical equipment.

 The interface of the electronic equipment has lower shock resistance and requires finer protection: SPD with UP not greater than 1.5kV is usually configured.

Location   Recommended UP
230/400V AC network 120/208VAC network
 Incoming line of main distribution ≤2.5Kv max ≤1.5Kv
 Electrical equipment ( switchboards, etc. ) 2.5Kv 1.5Kv
 Protected electronic equipment 1.5Kv 0.8kV

Figure 5

SPD coordination

If the line distance between the protected equipment and the first stage SPD is long ( more than 10m ) or the protected instrument is too precise, the two-stage coordinated SPD can reduce the oscillation overvoltage generated during surge transmission.  However, the minimum distance between two SPDs shall be greater than 5 m or a decoupling device shall be installed in the middle.

Recent News
Recommended products

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.